CVE-2023-2071 - CVE House
Back to Database
Status published Critical CVE-2023-2071

FactoryTalk View Machine Edition Vulnerable to Remote Code Execution

Vulnerability Description

Rockwell Automation FactoryTalk View Machine Edition on the PanelView Plus, improperly verifies user’s input, which allows unauthenticated attacker to achieve remote code executed via crafted malicious packets.  The device has the functionality, through a CIP class, to execute exported functions from libraries.  There is a routine that restricts it to execute specific functions from two dynamic link library files.  By using a CIP class, an attacker can upload a self-made library to the device which allows the attacker to bypass the security check and execute any code written in the function.

Impact Analysis

Refer to official advisory for detailed impact metrics.

Remediation

Ensure systems are updated to the latest vendor-supplied patch levels.

THREAT MONITOR

Am I Vulnerable?

Launch our assessment wizard to check if your infrastructure is exposed to • CVE-2023-2071

Credits & Attribution

The following person or organization is credited with identifying this vulnerability, as recorded in the NVD database:

  • Rockwell Automation would like to thank Yuval Gordon, CPS Research, and the Microsoft Threat Intelligence Community for reporting this vulnerability to us.

Affected Vendor

Rockwell Automation

View all reports →

Affected Software

Fa
Vulnerable Versions:
<=13.0

Timeline

Official Publish: September 12th, 2023
Last Modified: September 25th, 2024
Added to House: July 22nd, 2026

CVSS Vectors

V3: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H