CVE-2022-33174 - CVE House
Back to Database
Status published Critical CVE-2022-33174

Power Distribution Units running on Powertek firmware (multiple brands) before...

Vulnerability Description

Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext.

Impact Analysis

Refer to official advisory for detailed impact metrics.

Remediation

Ensure systems are updated to the latest vendor-supplied patch levels.

THREAT MONITOR

Am I Vulnerable?

Launch our assessment wizard to check if your infrastructure is exposed to • CVE-2022-33174

Credits & Attribution

No credits recorded in the NVD database.

Affected Vendor

powertekpdus

View all reports →

Affected Software

basic pdu firmware, pm pdu firmware, piml pdu firmware, smart pim firmware, smart pos firmware, smart pom firmware, smart poms firmware
Vulnerable Versions:
0

Timeline

Official Publish: June 13th, 2022
Last Modified: August 3rd, 2024
Added to House: July 21st, 2026

CVSS Vectors

V3: CVSS:3.1/AC:L/AV:N/A:H/C:H/I:H/PR:N/S:U/UI:N

Weaknesses (CWE)

No CWE data available

MITRE ATT&CK TTPs

No associated TTPs found for this vulnerability.