Power Distribution Units running on Powertek firmware (multiple brands) before...
Vulnerability Description
Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext.
Impact Analysis
Refer to official advisory for detailed impact metrics.
Remediation
Ensure systems are updated to the latest vendor-supplied patch levels.
Am I Vulnerable?
Launch our assessment wizard to check if your infrastructure is exposed to • CVE-2022-33174
Credits & Attribution
No credits recorded in the NVD database.
References
Affected Vendor
powertekpdus
View all reports →Affected Software
Timeline
CVSS Vectors
Weaknesses (CWE)
No CWE data available