An exploitable access control vulnerability exists in the data, program,...
Vulnerability Description
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability.Required Keyswitch State: REMOTE or PROG Associated Fault Code: 0001 Fault Type: Non-User Description: A fault state can be triggered by setting the NVRAM/memory module user program mismatch bit (S2:9) when a memory module is NOT installed.
Impact Analysis
Refer to official advisory for detailed impact metrics.
Remediation
Ensure systems are updated to the latest vendor-supplied patch levels.
Am I Vulnerable?
Launch our assessment wizard to check if your infrastructure is exposed to • CVE-2017-14464
Credits & Attribution
No credits recorded in the NVD database.
More from Talos
View All →Affected Vendor
Talos
View all reports →Affected Software
Timeline
CVSS Vectors
Weaknesses (CWE)
No CWE data available
MITRE ATT&CK TTPs
No associated TTPs found for this vulnerability.